Measures reported by UpsStatusTest

The UpsStatusTest monitors the current status of a target APC UPS, and reports a wide variety of performance statistics pertaining to that UPS.

Measurement Description Measurement Unit Interpretation
Ups_status The current state of the UPS   This measure reports the following states while indicating the current state of the UPS.
  • Off
  • Unknown
  • OnLine
  • On Battery
  • On Smart Boost
  • Timed Sleeping
  • Software Bypass
  • Rebooting
  • Switched Bypass
  • Hardware Failure Bypass
  • Sleeping Until Power Return
  • On Smart Trim
The numeric values that correspond to the above-mentioned states are as follows:
Value State
0 off
1 Unknown
3 onBattery
4 onSmartBoost
5 timedSleeping
6 softwareByPass
8 rebooting
9 switchedBypass
10 hardwareFailurebypass
11 sleepingUntilpowerReturn
12 onSmartTrim
100 online

Note:

By default, this measure reports the above-mentioned states while indicating the current state of the UPS. However, the graph of this measure will be represented using the corresponding numeric equivalents of the states as mentioned in the table above.
Input_voltage The current utility line voltage Volts  
Input_frequency The current input frequency to the UPS system Hz  
Output_voltage The current output voltage of the UPS system Volts  
Output_frequency The current output frequency of the UPS system Hz  
Output_load Indicates the current output load percentage of the UPS system. percent  
Output_current The current drawn by the load on the UPS Amps This measure is directly proportional to the current output load percentage of the UPS.