| Measurement |
Description |
Measurement Unit |
Interpretation |
| Input_Frequency |
Indicates the utility line frequency in tenths of Hz. |
Hz |
|
| Input_Line_Bads |
Indicates the number of times the Input was out of tolerance. |
Number |
|
| Input_Source |
Indicates the current external source of input power.
|
Number |
This measure can take any of the following values:
| Value |
Description |
| 1 |
Other |
| 2 |
None |
| 3 |
PrimaryUtility |
| 4 |
BypassFeed |
| 5 |
SecondaryUtility |
| 6 |
generator |
| 7 |
flywheel |
| 8 |
fuelcell |
|
| Output_Frequency |
Indicates the UPS output frequency in tenths of Hz. |
Hz |
|
| Adv_Output_Load |
Indicates the UPS output load in percent of rated capacity. |
Percent |
|
| output_Source |
Indicates the current source of output power. |
Number |
This measure can take any of the following values:
| Value |
Description |
| 1 |
Other |
| 2 |
None |
| 3 |
Normal |
| 4 |
Bypass |
| 5 |
Battery |
| 6 |
Booster |
| 7 |
Reducer |
| 8 |
ParallelCapacity |
| 9 |
ParallelRedundant |
| 10 |
HighEfficiencyMode |
|
| Bypass_Frequency |
Indicates the bypass frequency in tenths of Hz. |
Hz |
|