Measures reported by XupsBatStatTest
This Test reports the status of the Battery.
The measures made by this test are as follows:
| Measurement |
Description |
Measurement Unit |
Interpretation |
| Bat_Time_Remaining |
Indicates the battery run time in seconds before UPS turns off due to low battery. |
Secs |
|
| Bat_Voltage |
Indicates the battery voltage. |
Volts |
|
| Bat_Current |
Indicates the battery current. |
Amps |
The status of the current is positive when discharging the battery and the status of the current is negative when recharging the battery. |
| Bat_Capacity |
Indicates the charge of the battery in percentage. |
% |
|
| Bat_Abm_Status |
Indicates the status of the Advanced Battery Management. |
Number |
This measure can take any of the following values:
| Value |
Description |
| 1 |
Battery Charging |
| 2 |
Battery Discharging |
| 3 |
Battery Floating |
| 4 |
Battery Resting |
| 5 |
unknown |
|
|